G100 Ethernet IP Setup

G100 Ethernet IP Setup

 After installing the Ethernet IP card on a G100 the below steps should be followed for proper setup and operation. 

When controlling the VFD over Ethernet. Set...

  1. Drv=4 Field Bus
  2. Frq=8 Field Bus

 Setup Network addressing with the below parameters.


 The below input and output instance settings should match the PLC or an error will occur.

 Input Instance (CM-23)



Output Instance (CM-24)

Also set CM-25=0 to disable Rapienet

Lastly, set CM-94=1 to perform a comm. update.

The following below is information regarding G100 Ethernet Option Card setup:

 

G100 Ethernet Manual:

https://drive.google.com/file/d/1iyjM_ZBWc5xpZn0JArUC1coxeAlGaq8J/view?usp=sharing

 LS AC Drive communications save parameter (zohodesk.com)