LS AC Drive communications save parameter

LS AC Drive communications save parameter

  1. The communications save parameter function is performed through active drive serial communications/ fieldbus connection. 
    1. As parameters set during communication transmission are saved in RAM, the setting values will be lost if the power turns off and on. When setting parameters during communication transmission, select “1 (Yes)” at the following Table below as outlined to save the communications parameters.
    2. Most parameters set in the drive parameter CM/COM Groups, including the Ethernet (IP) Address would also be permanently saved with the following LS drive parameters identified below. 
    3. Do not use this Communication Update process when the inverter is working (operating the motor)  or during cyclic "active" network communications.
LS AC Drive Communication Save Parameter Table:

**  M100 With a remote keypad connected to the inverter of same series and firmware, drive parameters that were prior saved can be stored in a remote keypad by setting the DR.85 to a 1 or can be copied from the remote keypad to the inverter by setting the DR.86 to a 1.
  1. EXAMPLE:  LS Electric H100 or H100+ Model AC Drive: