What EMPRs have the Auto-reset function?

What EMPRs have the Auto-reset function?

GMP series EMPRs with the "A" designator feature an automatic reset function. Reference to the below list of model #s with the auto-reset.

Model

3802009500

GMP22-2PA 1.5A  110/220V 1a1b (Sol) EXP

3802009600

GMP22-2PA 5A 110/220V 1a1b (Sol) EXP

3802009700

GMP22-2PA 22A 110/220V 1a1b (Sol) EXP

3804005700

GMP40-2PA 20A  110/220V 1a1b (Sol) EXP

3804005800

GMP40-2PA 40A 110/220V 1a1b (sol) EXP

3806011700

GMP60-TA 6A  110V 1c[R] EXP

3806011800

GMP60-TA 30A  110V 1c[R] EXP

3806011900

GMP60-TA 60A  110V 1c[R] EXP

3806012000

GMP60-TA 6A  220V 1c[R] EXP

3806012100

GMP60-TA 30A  220V 1c[R] EXP

3806012200

GMP60-TA 60A  220V 1c[R] EXP

3806016900

GMP60-TA 6A  110V 1c[N] EXP

3806017000

GMP60-TA 30A  110V 1c[N] EXP

3806017100

GMP60-TA 60A  110V 1c[N] EXP

3806017200

GMP60-TA 6A  220V 1c[N] EXP

3806017300

GMP60-TA 30A  220V 1c[N] EXP

3806017400

GMP60-TA 60A  220V 1c[N] EXP


Specifications
GMP22 / 40-2PA (automatic reset) specification
1) Auto reset time: Auto reset within 1 minute
2) Automatic reset operation: Automatic reset only during overcurrent operation
-Automatic reset is performed within 60 seconds only in overcurrent operation
-No automatic reset is performed within 60 seconds during an open phase condition


GMP60TA (automatic reset) specification
1) Protection element: overcurrent
      Over-current Spec: Trip within 5 seconds when over 105%
   - The O-time setting dial is used to adjust automatic reset time (0, 20, 40, 80, 120 seconds): O-time is always fixed at 5 seconds
   -Automatic reset is performed at the set auto reset time in case of over current
2) Operating Time
  -Over-current operation delay (D-TIME) time: same as GMP60T
  -Over-current operation time: within 5 seconds
  -Auto reset time: 0 ~ 120 seconds (the existing O-TIME KNOB is changed to A-TIME KNOB)
   -The existing O-TIME is fixed within 5 seconds