This article is made to address the misunderstanding about the length of the set screws for the lugs within the UTS250 MCCBs.
Lug binding screw rating dualization:
If the UTS250 breaker is rated for 150-175A the length of the lug will be 16.6mm
If the UTS250 breaker is rated for 200-250A the length of the lug will be 10.2 mm