Purpose
This application note shows the simple steps involved in setting up a permanent magnet (PM) motor on an S100 drive. All S100’s with firmware version 2.50 or greater support PM motor control.
Parameters
Setup
the parameters below. Note that some parameter settings are based on the motor
nameplate. The nameplate in this
document is only an example. It is
imperative to have access to the motor nameplate in order to program in the
proper values into the drive and perform an auto-tune. It is also recommended to use the LCD keypad
for ease of programming.
Code No. |
Display |
Set Value |
|
DRV-09 |
Control Mode |
6: PM Sensorless |
|
DRV-14 |
Motor Capacity |
Select the kW setting closest to the motor rating. (kW=HPx.746)
|
|
DRV-18 |
Base Freq |
Base HZ from nameplate |
|
DRV-20 |
Max Freq |
Maximum frequency from nameplate
|
|
BAS-11 |
Pole Number |
Motor poles
from nameplate |
|
BAS-13 |
Rated Curr |
Rated amps (FLA) from nameplate
|
|
BAS-15 |
Rated Volt |
230V or 460V dependent on drive’s voltage class |
|
BAS-19 |
AC Input Volt |
Set to the input power supply’s voltage
|
Example motor nameplate with necessary information highlighted. |
Once the above parameters are properly set, start an auto-tune by setting BAS-20= 7 All (PM). The motor must be connected to the drive for this process. Typically auto-tuning will take about two minutes. Once completed BAS-20 will return to a setting of “None”.
Test Operation
Below are the parameters necessary to run the drive in Local control to test motor operation.
Code No. |
Display |
Set Value |
DRV-01 |
Cmd Frequency |
Desired speed (Hz) |
DRV-06 |
Cmd Source |
0: Keypad |