Setting up an S100 with a Permanent Magnet Motor

Setting up an S100 with a Permanent Magnet Motor

Purpose

This application note shows the simple steps involved in setting up a permanent magnet (PM) motor on an S100 drive.  All S100’s with firmware version 2.50 or greater support PM motor control.

 
Parameters

Setup the parameters below. Note that some parameter settings are based on the motor nameplate.  The nameplate in this document is only an example.  It is imperative to have access to the motor nameplate in order to program in the proper values into the drive and perform an auto-tune.  It is also recommended to use the LCD keypad for ease of programming.

 

Code No.

Display

Set Value

DRV-09

Control Mode





Example motor nameplate with necessary information highlighted.


6: PM Sensorless

DRV-14

Motor Capacity

Select the kW setting closest   to the motor rating.

(kW=HPx.746)

DRV-18

Base Freq

Base HZ from nameplate

DRV-20

Max Freq

Maximum frequency from

nameplate

BAS-11

Pole Number

Motor poles from nameplate

BAS-13

Rated Curr

Rated amps (FLA) from

nameplate

BAS-15

Rated Volt

230V or 460V dependent on drive’s voltage class

BAS-19

AC Input Volt

Set to the input  power

supply’s voltage

Example motor nameplate with necessary information highlighted.

 

Auto-tuning

Once the above parameters are properly set, start an auto-tune by setting BAS-20= 7 All (PM). The motor must be connected to the drive for this process.  Typically auto-tuning will take about two minutes.  Once completed BAS-20 will return to a setting of “None”.

  

Test Operation

Below are the parameters necessary to run the drive in Local control to test motor operation.

 

Code No.

Display

Set Value

DRV-01

Cmd Frequency

Desired speed (Hz)

DRV-06

Cmd Source

0: Keypad