Problem Description
A parameter in the drive is set to IP20, but it should be set to IP66. The drive cannot recognize the correct fan configuration with the incorrect setting.
Detecting the Problem
If the S100 is displaying the below code on the keypad, perform the steps in the Correction Process.
Correction Process
1. Press the RIGHT arrow to display “dr. 0”
2. Press the DOWN arrow until “dr.95” is displayed
3. Press ENTER
4. Press the LEFT arrow until “MA.0” is displayed
5. Press the DOWN arrow until MA.58 is displayed
6. Press ENTER
7. Power cycle the drive
8. Complete. Run the VFD and verify the Fan warning is gone.