Minimum Current Reading for ETM trip unit on MCCBs

Minimum Current Reading for ETM trip unit on MCCBs

Minimum Current Reading for ETM Trip Unit on MCCBs

Current Display Range

  • Minimum Current ≥ 0.3 × In
  • Maximum Current ≤ 10 × In

The current meter display range for ETM trip units is limited between 30% of the rated current (In) and up to 10 times the rated current.

For ETM trip unit products, the minimum measurable current is 0.3 × In.

Depending on operating conditions and the application environment, values lower than 0.3 × In may occasionally appear on the display. However, readings below this threshold are outside the guaranteed measurement range and their accuracy cannot be guaranteed.