Megger Test on ACB

Megger Test on ACB

1. Test method

1) ACB Close: Measurement between phases of main circuit

EUT’s contacts condition

Voltage applied to

Earth connected to

Remark

Closed

AaCc(Nn)

BbF

Phase

 


2) ACB OFF: Measure between poles of main circuit

EUT’s contacts condition

Voltage applied to

Earth connected to

Remark

Open

ABC(N)

abc(n)F

Pole

 

2.

When measuring ACB alone, 500 V should be applied to measure 100 ㏁ or more.

It is 10 ㏁ or more when measured as a whole switchboard

When measuring, there is no problem as long as you observe the measurement area according to the ACB Close/Off status.