1. Test method
1) ACB Close: Measurement between phases of main circuit
EUT’s contacts condition |
Voltage applied to |
Earth connected to |
Remark |
Closed |
AaCc(Nn) |
BbF |
Phase |
2) ACB OFF: Measure between
poles of main circuit
EUT’s contacts condition |
Voltage applied to |
Earth connected to |
Remark |
Open |
ABC(N) |
abc(n)F |
Pole |
2.
When measuring ACB alone, 500 V should be applied to measure 100 ㏁ or more.
It is 10 ㏁ or more when measured as a whole switchboard
When measuring, there is no problem as long as you observe the measurement area according to the ACB Close/Off status.