How does the M100 and G100 connect to DriveView?
The M100 and G100 have a couple options for connecting to DriveView 9 software.
When using either of the below cables your baud rate in Driveview 9 should match the baud rate on the VFD set at CM.03
Be sure to set the connection type to "Modbus-RTU" and the com port baud rate setting to match CM.03.
Option 1: The most direct and easiest way is to use the below USB to Serial Cable.
Item Code
|
Description
|
64090354
|
INV,RS485 to USB Converter,T485-LSLV
|
Take note that the cable is "USB to RS485". The S100 cable is very similar but is not compatible.
Option 2: A 3rd party RS485 USB converter may be used. The below example would require wiring the + and - terminals on the adapter to S+ and S- terminals on the VFD.