How do I set a high (over 60Hz) max frequency on the C100?

How do I set a high (over 60Hz) max frequency on the C100?

There are a few parameters which are required to overspeed the VFD past 60Hz. First off, you will need to change the VFD maximum speed limits. Next, you need to scale your analog input (if used). If you are using the keypad for frequency control, you just need to setup a speed limit. 

Speed Limits
  1. F21=Max speed
  2. F24=1
  3. F25=Max speed
Analog Inputs
  1. V2 (built-in POT) set max frequency at I5
  2. AI (0-10VDC) set max frequency at I10
  3. AI (4-20mA) set max frequency at I15
Example
An application requires 120Hz maximum frequency with a 4-20mA reference. Below is the required parameters
  1. F21=120.0
  2. F24=1
  3. F25=120.0
  4. I15=120.0