How do I run my motor faster than 60Hz?
Some applications require that the motor runs faster than 60Hz. By default LSIS VFDs limit speed to 60Hz. To increase this, see the below parameters.
G100, S100, iS7, and H100 Setup
- dr/DRV20 = Desired Maximum Frequency
- Ad/ADV24 = Minimum/ Maximum Speed Adjustment, Enable
- Ad/ADV25 = Minimum Speed
- Ad/ADV/26 = Maximum Speed
- In/IN01 = Analog Input Maximum Speed (Only if utilizing AI (0-10vdc,4-20ma or Speed Pot)
If you are controlling speed reference VIA an analog input you must also set your desired max speed at parameter IN01.
M100 Setup
- FrM=Desired Maximum Frequency
If you are controlling speed VIA an analog input set the appropriate parameter to the desired Max frequency. In11 for V1 or In56 for I2