H100 will not start after a power loss

H100 will not start after a power loss

By default, as a safety precaution, the VFD will not start after a momentary or extended power loss without cycling the RUN command. Adjusting the below listed parameters will fix this issue.

Required Settings
ADV10=1 -Yes
CON71=0100 See setup for LED keypad below.
PRT08=11 (both virtual dip switches up)