H100 / SP100 Easy Start process Application Macro Define
While user performing the initial Quick Start process for a new LS Electric H100 or SP100 AC Drive.
Unless requirement for special Pump or Fan application, please keep Application Macro defined to BASIC. If this Macro is changed to any other Application Macro define, there will many other drive parameters that will automatically make change to a different setting and possibly affecting drive performance and also changing users requirement for their installation needs.
To check or change H100/ SP100 Macro define, please refer to parameter CNF-43. Macro is factory set to BASIC.
If user would like to perform the Easy Start process anytime (as long as the drive is in stop and not operating the motor). Select Parameter CNF-61, set to a "1" = yes.
Last, the Application Macro will NOT default to BASIC during a parameter initialization, CNF-40. One must manually make change to CNF-40 to BASIC.