Cannot connect multiple VFDs over Ethernet

Cannot connect multiple VFDs over Ethernet

When setting up more than one VFD with an Ethernet card that supports Rapienet+ you may have issues with connection and control.  To fix the issue is is recommended to disable Rapienet+ at parameter CM25. 

  1. Go to CM25, this defaults to 2 - Rapienet+ Enabled. 
  2. Change this to 0 - Rapienet+ disabled. (Press enter twice on G100)
  3. Navigate to CM94. 
  4. Change CM94=1 to save the communication change. (Press enter twice on G100)