This article goes over how to manually adjust the Ir settings on an LS smart trip unit.
Part 1: Set STU to local
Step1; Press H/W Set
Step 2: Press Local/Remote Control
Step 3: Enter password (if none already set, press okay)
Step 4: Set to Local
Step 5: Press return button to go back to main screen
Part 2: Changing Ir setting.
Step 1: Press Relay Set
Step 2: Press L
Step 3: Press right arrow key
Step 4: Set Ir to desired setting
NOTE 1: The Ir dial is the default. If it is changed, it will overwrite the value set on the display.
NOTE 2: The keypad offers a small range. First set the dial near your desired setting, then fine tune to your desired value using keypad.
Step 5: Press the return key and save the value by pressing OK
Here is a video walk through: