Applying Single-Phase Power to the H100 Drive
The H100 series Drive is UL listed (File E124949) to run off of single phase power if necessary. An approximate 50% derate needs to be applied when sizing the H100 for single phase input applications. Reference to the below table for drive sizing and selection.
Single Phase Input Specifications
![](https://img.zohostatic.com/zde/static/images/exclamation.png)
Take note of the higher input amp ratings as this will affect input wire gauge and branch circuit protection sizing.
Wiring
![](https://desk.zoho.com/DocsDisplay?zgId=632093292&mode=inline&blockId=2oxsa94a635b77faa4884bc850a8053773b3e)
And make sure that LSE AC Drive parameter DR.14 is set to
correct HP/KW of motor applied in your application.