Applying Single-Phase Power to the S100 Drive

Applying Single-Phase Power to the S100 Drive

The S100 series Drive is UL listed (File E124949) to run off of single-phase power if necessary. An approximate 50% derate needs to be applied when sizing the S100 for single phase input applications. Reference to the below table for drive sizing and selection.

Single Phase Input Specifications
Take note of the higher input amp ratings as this will affect input wire gauge and branch circuit protection sizing.




Wiring





And make sure that LSE AC Drive parameter DR.14 is set to correct HP/KW of motor applied in your application.