For ERMS, units are shipped with the default setting as “No Trip.”
Therefore, when using P-type or S-type STU, the OP Mode must be changed to “Trip” on the STU screen.
For A-type, the OP Mode must be changed to “Trip” using the software in order for ERMS tripping to function properly.
Additionally, the Use/Not Use setting must be set to “Use.”